⟵ Return to Learn

Testing

Disclaimer: The attached information represents tension loads or loads applied to the product in an upward direction, perpendicular to the roof surface. Roof assemblies must be secured in accordance with typical roof industry installation practices and attachment patterns specified in the individual test report selected. Third party test reports are available for both tension as well as shear for each roof assembly. Loads are listed in ultimate force without the inclusion of a safety factor. Allowable loads should be calculated using a safety factor consistent with ASCE7 and ASTM D6630. Actual safety factor identification and overall force load calculations are the responsibility of the qualified design professional of record for each project.

 
Testing-Photo-1-150x150.jpg
Testing-Photo-3-150x150.jpg
Testing-Photo-2-150x150.jpg